100003646中文資料圖爾克數(shù)據(jù)手冊PDF規(guī)格書
100003646規(guī)格書詳情
The 2-channel temperature measuring amplifier IMX12-TI02-2TCURTDR-2I-CPR/24VDC
has inputs for: Thermocouples acc. to IEC
60584, DIN 43710, GOST R 8.585-2001, low
voltages (-150…+150 mV), RTDs acc. to IEC
60751, DIN 43760, GOST 6651-94 (2, 3-wire)
and resistors 0…5 kò (2, 3-wire). The device
can be powered from a power bridge that also
transmits a collective fault signal.
The cold junction compensation can be set to
internal, external, or to a constant value. The
device is configured via the PC interface. The
current outputs can be set to 0/4 … 20 mA
and source or sink.
A green LED indicates operational readiness.
A fault in the input circuit leads to a flashing
red LED according to NE44, an internal error
to a steady read LED. The fault current can be
adjusted to 21.5 mA.
The device can be used in safety circuits up
to SIL2 (high and low demand according to
IEC 61508) and meets the requirements of
the NE21. It is equipped with removable screw
terminals.
The device is equipped with removable screw
terminals.
■ Input circuits monitored for wire-break and
short-circuit
■ Parameterized via PC
■ Complete galvanic isolation
■ Input reverse-polarity protected
■ Removable screw terminals
■ Power bridge (connector incl. in delivery)
■ ATEX, IECEx, cFM,cUL, NEPSI, INMETRO, Kosha, TR CU EAC CMI, TS
■ Installation in zone 2
■ SIL 2